Hover to Zoom
Electrical data | |
---|---|
Nominal input voltage | 220…240 V |
Mains frequency | 50…60 Hz |
Input voltage AC | 198…264 V |
Input voltage DC | 176…276 V |
Total harmonic distortion | < 10 % |
Power factor λ | 0.95 |
ECG efficiency | 88 % |
Device power loss | 2.4 W |
Power loss in stand-by mode | ≤0.27 W |
Inrush current | 5 A |
Max. ECG no. on circuit breaker 10 A (B) | 82 |
Max. ECG no. on circuit breaker 16 A (B) | 130 |
Max. ECG no. on circuit breaker 25 A (B) | - |
Surge capability (L/N-Ground) | 1 kV |
Nominal output voltage | 7.5…54 V |
U-OUT (working voltage) | 60 V |
Nominal output current | 150…1050 mA |
Output current tolerance | ±3 % |
Output ripple current (100 Hz) | < 2 % |
Nominal output power | 18 W |
Galvanic isolation | SELV |
Dimensions & weight | |
---|---|
Length | 95.0 mm |
Width | 53.0 mm |
Height | 30.0 mm |
Product weight | 100.00 g |
Cable cross-section, input side | 0.2…1.5 mm² |
Cable cross-section, output side | 0.2…1.5 mm² |
Wire preparation length, input side | 8.0…9.0 mm |
Wire preparation length, output side | 8.0…9.0 mm |
Colors & materials | |
---|---|
Casing material | Plastic |
Temperatures & operating conditions | |
---|---|
Ambient temperature range | -20…+50 °C |
Maximum temperature at tc test point | 75 °C |
Max.housing temperature in case of fault | 100 °C |
Permitted rel. humidity during operation | 5…85 % |
Lifespan | |
---|---|
ECG lifetime | 50000 / 100000 h |
Additional product data | |
---|---|
Encapsulated | No |
Capabilities | |
---|---|
Dimmable | Yes |
Dimming interface | DALI / Touch DIM / Touch DIM Sensor |
Dimming range | 1…100 % |
Dimming method | Amplitude Modulation |
Constant lumen function | Programmable |
Overheating protection | Automatic reversible |
Overload protection | Automatic reversible |
Short-circuit protection | Automatic reversible |
No-load proof | Yes |
Max. cable length to lamp/LED module | 2.0 m |
Suitable for fixtures with prot. class | I / II |
Suitable for emergency lighting | Yes |
Type of connection, output side | Push terminal |
Programmable features | |
---|---|
Operating Current | Yes |
Tuning Factor | No |
Constant Lumen | Yes |
Lamp Operating Time | Yes |
Driver Guard | No |
DALI Settings | Yes |
Emergency Mode | Yes |
Luminaire Info | No |
Configuration Lock | No |
Soft Switch Off | Yes |
Dim to Dark | Yes |
TouchDIM + Sensor | Yes |
Corridor Functionality | Yes |
Tunable White CCT | No |
Tunable White High precision | No |
OEM Key | Yes |
Certificates & standards | |
---|---|
Approval marks – approval | ENEC 10 / VDE / EMC / EL / CE |
Standards | Acc. to EN 61347-1/Acc. to EN 61347-2-13/Acc. to EN 55015/Acc. to EN 61547/Acc. to EN 61000-3-2/Acc. to EN 62384 |
Protection class | II |
Type of protection | IP20 |
Logistical data | |
---|---|
Temperature range at storage | -25…85 °C |
Untuk keterangan lebih lanjut, silahkan download PDF ini :